shop.pierobersanini.com uses technical "first party" and "third parties" cookies to ensure the technical functioning and to improve the browsing experience of the website. shop.pierobersanini.com uses analytical "third party cookies" cookies in order to collect statistical information about the website visits. For further information or to completely or partially refuse the use of cookies, please see our cookie policy. By continuing your navigation, you agree to the use of cookies.
close
freeshipping Free shipping (over € 100,00) i.e.
×

Item added to cart

BACK TO SHOP VIEW CART

STATUS Convertitori con funzione di calcolo e funzioni speciali

SEM1750

Code STSEM1750



in stock Available

Quantity
- +

Price
€ 269,02

ADD TO CART

Technical specifications
SEM1750
Dual Channel mA / voltage on input and output with Maths functions 

Dual channel voltage or current (Active/Passive) inputs and outputs
5 Port isolation to 3.75Kv
Universal Power Supply
Can be configured as an active signal splitter
Maths function on each output 
Signal linearisation
Signal Simulate Function For Diagnostics
Direct USB Configuration
Description
The SEM1750 is a dual channel signal conditioner designed to accept mA or voltage inputs and provide isolated, industrial process output signals in mA or Volts.  
Each output channel may be linked to either an input signal or to a maths function of both input signals. 
This powerful feature allows the device to operate in several different modes.
The product has transmitter power supplies built into each input so can power temperature, pressure, level, humidity etc transmitters. 
Using maths functions in the device, average, sum, highest, lowest can be selected to provide a function of the two input signals.
It can also be used as a splitter, dual channel isolator and has a user non linear feature to allow, for example, tank measurement. 
So, for example, you could have two level sensors connected to two non linear tanks.  
The product can linearise the tank’s volume to the output signal.  Then, if required you could do maths functions on the linearised outputs such as average, difference etc.
The output signal(s) can also be programmed for any value between (0 to 20) mA or (0 to 10) V.